Wire Fire Resistance Test Machine, IEC 60331 - Qinsun
Fabricant professionnel d'instruments de détection
Ligne directrice nationale de consultation :+86 021-64208466
Produits

Wire Fire Resistance Test Machine, IEC 60331

Description:Fire-resistant cable refers to the cable that can keep a safe running time in the c

WhatsApp : +86 13816217984

Email : info@qinsun-lab.com

Contenu

Description:

Fire-resistant cable refers to the cable that can keep a safe running time in the case of flame combustion.

TESTECH Fire Resistance Tester is designed according to the requirements of  IEC60331-11.and used to obtain the refractory characteristics of a fire resistant cable or optical cable under flame conditions.

Standards:

• IEC 60331 Part 11

• IEC 60331 Part 21

User' s Experience:

1. This cabinet is made of stainless steel, anti-smoke and gas corrosion.

2. The control system is designed with a high degree of automation, automatic ignition, temperature and time digital display, convenient to observe and record, stable and reliable.

Main Features:

1. All fixtures are made of stainless steel;

2. The burner is a belt type propane blowtorch with a Venturi mixer, and the burner nozzle is length 500mm, width 15mm;

3. Those burning holes are staggered into 3 rows, and the front width is 15mm, holes diameter is 1.32mm and these holes center distance is 3.2mm;

5. One end of the specimen holder is equipped with a clamp to fix the sample, and the other end is convenient for heat transfer along the longitudinal specimen;

6. The cable sample is supported by two metal rings, and the middle length of the two rings is about 300mm;

7. An inner diameter of the sample supporting metal rings is 150mm, and the cross-sectional diameter of the ring is 10 ± 2mm.

8. The position of the burner torch from burning the bottom is not less than 200mm, and not less than 300mm from the tank wall.

Combustion System:

1. Independent standard electrical control platform;

2. With intelligent detection function, when a short circuit in the sample during the test, automatic alarm and turn off the fire source.

3. Fuse current in the experimental circuit is 2A;

4. The sample is applied to power of AV 100V ~ 1000V adjustable;

5. The time can be set free for the fire, the time recommended by standards is 90min.

Device parameters:

1. Voltage: AC 380V 3-phase, 50 / 60Hz, 30A;

2. The input voltage 0 ~ 1000V; can be adjusted;

3. The breakdown current is 2A;

4. Maximum power: 5000VA;

5. Timer: 0 ~ 999min

6. The flame temperature of 0 ~ 1100 ºC adjustable;

7. The test load current is 0.25A, can be adjusted;

Specification:

ModelFTech-IEC60331A
Size1.600 (W) × 850 (D) × 1.650 (H) mm
Console Size600 (W) × 750 (D) × 1.200 (H) mm
PowerAC 380V 3-phase, 50 / 60Hz, 30A
Weight300kg
ManualSupplied
 

Disclaimer: Le contenu ci-dessus est destiné à des fins de référence et de communication uniquement entre les initiés de l'industrie, et ne garantit pas son exactitude ou son exhaustivité. Conformément aux lois et règlements pertinents et aux règlements de ce site Web, les unités ou personnes qui achètent des articles connexes doivent obtenir des qualifications et des conditions de qualification valides.


Message en ligne

Détails de contact

Téléphone de l'entreprise

+86-21-6420 0566

Heures de travail

Du lundi au vendredi

Téléphone portable:

13816217984

Courriel :

info@qinsun-lab.com

Code QR